1 1/2" (38 mm) Australian Firefighting Layflat Delivery Hose — 100m Friction Loss Chart & Calculator
ID-measured 38 mm Australian CFA/RFS-style layflat firefighting delivery hose. Rated 1000 kPa working / 1200 kPa max with 38 mm true bore—delivers ~3x lower friction loss per metre than 1" fire hose at 150–250 L/min. Standard 38 mm Camlock, BIC, or Storz couplings.
- True Mean ID
- 38 mm
- Outside Dia (OD)
- 45 mm
- Wall Thickness
- 3.5 mm
- PN Rating (20°C)
- 1200 kPa 122 m max · 1000 kPa warn
- Derated (40°C)
- 1200 kPa Reinforced hose
- Safe Flow ≤1.5 m/s
- 102 L/min Hammer >163 L/min
- Fitting System
- Camlock, Storz, BIC or BSP Hose Tail
1 1/2" Fire Hose (38 mm) Friction Loss & Velocity Chart over 100 Metres
ID: 38 mm · ε = 0.005 mm · Hazen-Williams C = 140
| Flow (L/min) | Flow (L/hr) | Velocity (m/s) | Darcy Head (100m) | Darcy Drop (kPa) | Hazen-W C=140 (m) | Drop (PSI) | Safety Status |
|---|---|---|---|---|---|---|---|
| 10 | 600 | 0.15 | 0.11 m | 1.0 kPa | 0.09 m | 0.2 psi | Safe (≤1.5 m/s) |
| 20 | 1,200 | 0.29 | 0.35 m | 3.4 kPa | 0.34 m | 0.5 psi | Safe (≤1.5 m/s) |
| 40 | 2,400 | 0.59 | 1.18 m | 11.6 kPa | 1.23 m | 1.7 psi | Safe (≤1.5 m/s) |
| 60 | 3,600 | 0.88 | 2.43 m | 23.8 kPa | 2.60 m | 3.5 psi | Safe (≤1.5 m/s) |
| 80 | 4,800 | 1.18 | 4.06 m | 39.8 kPa | 4.43 m | 5.8 psi | Safe (≤1.5 m/s) |
| 100 | 6,000 | 1.47 | 6.06 m | 59.4 kPa | 6.69 m | 8.6 psi | Safe (≤1.5 m/s) |
| 120 | 7,200 | 1.76 | 8.41 m | 82.5 kPa | 9.38 m | 12.0 psi | Caution (1.5–2.4 m/s) |
| 140 | 8,400 | 2.06 | 11.11 m | 108.9 kPa | 12.48 m | 15.8 psi | Caution (1.5–2.4 m/s) |
| 160 | 9,600 | 2.35 | 14.15 m | 138.8 kPa | 15.98 m | 20.1 psi | Caution (1.5–2.4 m/s) |
| 180 | 10,800 | 2.65 | 17.53 m | 171.9 kPa | 19.87 m | 24.9 psi | Water Hammer (>2.4 m/s) |
| 200 | 12,000 | 2.94 | 21.23 m | 208.2 kPa | 24.15 m | 30.2 psi | Water Hammer (>2.4 m/s) |
Notes: Friction figures represent straight-pipe major losses only (20°C clean water, Colebrook-White Darcy-Weisbach). Add static elevation, suction lift, outlet pressure, and minor fitting losses (barbed elbows/joiners, foot valve, check valves) using the live calculator below.
Step up to 2" Suction/Delivery Hose & cut friction by 73.2%
Stepping up from 1 1/2" Fire Hose (38 mm) (38 mm ID) to 2" Suction/Delivery Hose (50 mm ID) cuts pipe friction by 73.2% (saving 3.0 m / 29 kPa) and lowers velocity from 1.18 to 0.68 m/s.
High-flow delivery & coupling discipline for 1 1/2" Fire Hose (38 mm)
1 1/2" (38 mm) Australian Firefighting Layflat Delivery Hose carries a 38 mm true bore with wall roughness ε = 0.005 mm (Hazen-Williams C = 140). Keep delivery hoses unkinked and ensure suction lines never exceed 5.5 m combined static lift + foot-valve friction.
1 1/2" Fire Hose (38 mm) vs Next Size Up (2" Suction/Delivery Hose) — 100 m Run
Length: 100 m · Static Rise: 10 m · Outlet: 100 kPa · Darcy-Weisbach (20°C)
Interactive 1 1/2" Fire Hose (38 mm) (100m) Pump & Friction Solver
Pre-loaded with 100 m of 1 1/2" (38 mm) Australian Firefighting Layflat Delivery Hose (38 mm ID) at 80 L/min. Adjust elevation, fittings, water temperature, and pump archetype below.
1. Pipe Standard & Size
44 AU SpecsID-measured 38 mm Australian CFA/RFS-style layflat firefighting delivery hose. Rated 1000 kPa working / 1200 kPa max with 38 mm true bore—delivers ~3x lower friction loss per metre than 1" fire hose at 150–250 L/min. Standard 38 mm Camlock, BIC, or Storz couplings.
2. Site Run & Hydraulic Conditions
Equivalent: 4,800 L/hr · 115,200 L/24h
3. Fittings & Valves (2)
ΣK = 4.65 · +7.9 m eq. pipe · 0.33 m loss
Suction Intake & Strainer
Directly increases pump suction head — critical for the 5.5 m cavitation & priming guardrail.
Highest single fitting loss in typical farm systems due to strainer mesh + hinged/poppet check flap on the suction side—critical for cavitation & 5.5 m suction lift checks! Oversizing suction line by one size cuts this penalty dramatically.
Loss: 0.32 m (3.1 kPa · +7.6 m eq.)
Delivery Fittings & Non-Return Valves
Note the steep minor-loss penalty of internal rural barbed inserts vs. full-bore external metric compression fittings.
Internal insert barb steps down inside the pipe wall (reducing local ID by ~4–6 mm), creating sudden contraction/expansion turbulence—nearly 5x the loss of an external metric compression joiner.
High minor loss caused by the dual restriction of an internal barbed spigot combined with an abrupt short-radius 90° direction change. Use sweeping pipe bends instead wherever trench layout allows.
Severe bore restriction from internal insert barbs plus 90° dividing/combining branch turbulence. Multiple barbed tees in series rapidly erode available pump head.
Full-bore external O-ring and split-ring grip seal—zero internal barb intrusion, keeping velocity profile smooth and minor loss minimal.
External compression body preserves full internal bore diameter through the 90° turn, cutting head loss by more than half versus a rural barbed elbow.
Full-bore external seal eliminates barb necking, leaving only the 90° branch turning loss (~half the K-factor of a barbed rural tee).
Lower head loss than spring-loaded check valves once flow lifts the flap fully open, but slower closure can trigger water-hammer slam on steep rising mains.
Higher resistance due to spring tension and poppet obstruction around the seat, but rapid non-slam closure prevents reverse-flow water hammer on steep hills and bore risers.
Isolation Valves
Low friction when fully open; avoid snapping quarter-turn ball valves shut on lines above 1.5 m/s.
True full-port ball bore aligns cleanly with pipe ID when open (negligible loss). Warning: never snap quarter-turn valves shut rapidly on high-velocity lines (>1.5 m/s) or severe water hammer will spike pipe pressure.
Loss: 0.01 m (0.1 kPa · +0.3 m eq.)
Gate retracts completely clear of the flow path when fully open, giving minimal friction loss. Slow multi-turn closure naturally protects PE poly mains against sudden water-hammer spikes.
Water velocity is 1.18 m/s, safely within the <= 1.5 m/s design range for low friction and minimal water hammer.
Total dynamic pressure (256 kPa) is safely within 1 1/2" Fire Hose (38 mm) working rating (1000 kPa warning / 1200 kPa max).
Total suction head is 1.82 m, safely below the 5.5 m cavitation & priming threshold.
Interactive System Curve vs. Australian Pump Curves
Click any pump chip below to overlay its H-Q curve, check shut-off pressure against pipe PN rating, and locate the exact duty point.
No Direct Rural-vs-Metric Naming Trap
1 1/2" Fire Hose (38 mm) (38 mm true ID) does not share an ambiguous Rural/Metric nominal pair. Standard rural Class B poly tops out at 2" (50.9 mm ID), whereas DN63–DN90 Metric PE100 pipes offer larger high-pressure bores.
Step Up to 2" Suction/Delivery Hose
Stepping up from 1 1/2" Fire Hose (38 mm) (38 mm ID) to 2" Suction/Delivery Hose (50 mm ID) cuts pipe friction by 73.2% (saving 3.0 m / 29 kPa) and lowers velocity from 1.18 to 0.68 m/s.
Recommended Australian Pump Archetypes (Ranked for Your System)
Exact bisection intersection between each pump's H-Q curve and your 100 m 1 1/2" Fire Hose (38 mm) system curve. Click any pump to inspect on the chart and verify dead-head pipe safety.
| Pump Archetype | Power | Solved Operating Duty Point | Shut-Off Head | Status | Est. AU Price | Compare |
|---|---|---|---|---|---|---|
2" Trash / Transfer PumpActive Strong match: delivers 87.9 L/min at 26.9 m head (1.29 m/s) safely within pipe pressure limits. | Petrol | 87.9 L/min @ 26.9 m 264 kPa · 1.29 m/s | 28 m (275 kPa) | Recommended Match | $450–$980 AUD | |
240V Multistage Irrigation Pump Strong match: delivers 130.9 L/min at 32.4 m head (1.92 m/s) safely within pipe pressure limits. | 240V AC | 130.9 L/min @ 32.4 m 318 kPa · 1.92 m/s | 62 m (608 kPa) | Recommended Match | $650–$1,450 AUD | |
Single-Impeller Fire Pump Meets target flow at 221.5 L/min (49.8 m head), but note: high velocity (3.25 m/s), oversized for target flow. | Petrol | 221.5 L/min @ 49.8 m 488 kPa · 3.25 m/s | 70 m (686 kPa) | Capable (Check Sizing) | $550–$1,150 AUD | |
Twin-Impeller Fire Pump Meets target flow at 245.7 L/min (55.7 m head), but note: high velocity (3.61 m/s), oversized for target flow. | Petrol | 245.7 L/min @ 55.7 m 546 kPa · 3.61 m/s | 98 m (961 kPa) | Capable (Check Sizing) | $850–$1,650 AUD | |
240V Tank Jet Pump Delivers 56.0 L/min (70% of 80 L/min target) at 24.0 m head. | 240V AC | 56.0 L/min @ 24.0 m 235 kPa · 0.82 m/s | 46 m (451 kPa) | Undersized Flow | $380–$780 AUD | |
Solar Bore Pump (24V/48V) Delivers 53.9 L/min (67% of 80 L/min target) at 23.9 m head. | Solar DC | 53.9 L/min @ 23.9 m 234 kPa · 0.79 m/s | 75 m (735 kPa) | Undersized Flow | $1,400–$3,200 AUD |
Bill of Materials (BOM) & Printable Engineering Spec Sheet
Standard Australian poly coil rollup, fitting-system compatibility guard, and counted hardware ready to hand to your rural supply branch.
+ 3 straight coil-to-coil joiners recommended to connect rolls.
Use 1 1/2" (38 mm ID) Australian Camlock, Storz, BIC, or BSP hose-tail couplings secured with heavy-duty T-bolt or Band-It clamps.
- 1 × 2" High-Flow Petrol Trash & Dam Transfer Pump$450–$980 AUDInlet 50 mm / Outlet 50 mm · Shut-off 28 m
- 1 × Suction Foot Valve & Strainer BasketK=4.50 · 0.32 m
- 1 × Full-Bore Quarter-Turn Ball Valve (Fully Open)K=0.15 · 0.01 m
As an Amazon Associate I earn from qualifying purchases. When you click links to various merchants on this site (including eBay Partner Network) and make a purchase, this can result in this site earning a commission.
Source Matched Pipe, Fittings & Pumps for This Spec
Links adapt dynamically to your chosen pipe family (1 1/2" Fire Hose (38 mm)) and active pump category (2" Trash / Transfer Pump) across Australian-stocked retailers.
Australian Petrol Firefighting & Bulk Transfer Pumps
GX-style single-impeller, twin-impeller high-head, and 2" trash transfer petrol pumps ready for rural delivery.
View Matching 2" Trash Transfer Pumps
Heavy-Duty Suction Hose, Fire Reels & Non-Return Foot Valves
Vacuum-rated 2" helical suction kits and 1"–1.5" layflat hoses with Australian Camlock and Storz fittings.
Price 110m of 1 1/2" Fire Hose (38 mm) + Camlock Kits
As an Amazon Associate I earn from qualifying purchases. When you click links to various merchants on this site (including eBay Partner Network) and make a purchase, this can result in this site earning a commission.
Engineering Q&A: 1 1/2" Fire Hose (38 mm) over 100 Metres
What is the maximum safe flow rate for 1 1/2" Fire Hose (38 mm) (38 mm ID)?
For continuous farm and irrigation service at or below the 1.5 m/s velocity guideline, 1 1/2" (38 mm) Australian Firefighting Layflat Delivery Hose (38 mm true internal diameter) safely carries up to 102.1 L/min (6,124 L/hr). Above 163.3 L/min (2.4 m/s), flow enters the water-hammer risk zone where rapid valve closure can spike pressure sharply.
How much friction head loss does 100m of 1 1/2" Fire Hose (38 mm) have at 80 L/min?
Over a 100 m run at 80 L/min (velocity 1.18 m/s, 20°C water), 1 1/2" Fire Hose (38 mm) loses 4.06 m of head (40 kPa / 5.8 PSI) via Darcy-Weisbach, compared with 4.43 m using Hazen-Williams (C=140).
What is the maximum pressure rating of 1 1/2" Fire Hose (38 mm) in hot Australian summer conditions?
1 1/2" (38 mm) Australian Firefighting Layflat Delivery Hose is rated to 1000 kPa continuous working pressure and 1200 kPa maximum (122.4 m head) using reinforced hose construction (not PE temperature-derated under AS/NZS 4130, though always inspect couplings and avoid kinks).
How much friction does stepping up from 1 1/2" Fire Hose (38 mm) to 2" Suction/Delivery Hose save over 100m?
At 80 L/min over 100 m, stepping up from 1 1/2" Fire Hose (38 mm) (38 mm ID) to 2" Suction/Delivery Hose (50 mm ID) cuts pipe friction loss by 73.2%—saving 2.97 m of head (29 kPa) and reducing water velocity from 1.18 m/s down to 0.68 m/s.